Component Database


Ventilation system (capacity < 600 m3/h)
Dantherm HCH 5

Component id: 0272vs03
Manufacturer: Dantherm Air Handling A/S
Air flow range from: 99 m3/h
To: 220 m3/h
Heat recovery rate: 81 %
Specific electric power: 0.27 Wh/m3
Efficiency ratio: 0.63
Humidity recovery: 0 %
Sound level of unit: 51.8 dB(A)
Climate zones: Cool, temperate

Leakage

Internal leakage: 0.55 %
External leakage: 0.8 %

Acoustic duct

Outdoor air: 62.2 dB(A)
Supply air: 59.2 dB(A)
Extract air: 57.8 dB(A)
Exhaust air: 68.6 dB(A)

Back to list