Component Database


Ventilation system (capacity < 600 m3/h)
Dantherm HCV 3

Component id: 0274vs03
Manufacturer: Dantherm Air Handling A/S
Air flow range from: 60 m3/h
To: 140 m3/h
Heat recovery rate: 80 %
Specific electric power: 0.29 Wh/m3
Efficiency ratio: 0.61
Humidity recovery: 0 %
Sound level of unit: 52.6 dB(A)
Climate zones: Cool, temperate

Leakage

Internal leakage: 0.59 %
External leakage: 1.8 %

Acoustic duct

Outdoor air: 62.9 dB(A)
Supply air: 58.7 dB(A)
Extract air: 57.7 dB(A)
Exhaust air: 66.7 dB(A)