Component Database


Ventilation system (capacity < 600 m3/h)
KWL EC 370

Component id: 0286vs03
Manufacturer: Helios Ventilatoren GmbH & CO KG
Air flow range from: 103 m3/h
To: 299 m3/h
Heat recovery rate: 84 %
Specific electric power: 0.36 Wh/m3
Efficiency ratio: 0.62
Humidity recovery: 0 %
Sound level of unit: 47.6 dB(A)
Climate zones: Cool, temperate

Leakage

Internal leakage: 0.42 %
External leakage: 1.93 %

Acoustic duct

Outdoor air: 44.7 dB(A)
Supply air: 59.5 dB(A)
Extract air: 42.4 dB(A)
Exhaust air: 58.5 dB(A)

Back to list