Component Database


Ventilation system (capacity < 600 m3/h)
HRmural UP ECO 400 / KWin

Component id: 1018vs03
Manufacturer: P. Lemmens Company S.A
Air flow range from: 105 m3/h
To: 267 m3/h
Heat recovery rate: 77 %
Specific electric power: 0.35 Wh/m3
Efficiency ratio: 0.55
Humidity recovery: 0 %
Sound level of unit: 61.3 dB(A)
Climate zones: Cool, temperate

Leakage

Internal leakage: 1.83 %
External leakage: 0.76 %

Acoustic duct

Outdoor air: 58.7 dB(A)
Supply air: 70.5 dB(A)
Extract air: 60.6 dB(A)
Exhaust air: 68.7 dB(A)

Back to list