Component Database

English Deutsch


Ventilation system (capacity < 600 m3/h)
LG 350 FV

Image of 1330vs03: LG 350 FV
Component id: 1330vs03
Manufacturer: J. PICHLER Gesellschaft m.b.H.
Air flow range from: 71 m3/h
To: 277 m3/h
Heat recovery rate: 85 %
Specific electric power: 0.22 Wh/m3
Efficiency ratio: 0.75
Humidity recovery: 76 %
Sound level of unit: 41.2 dB(A)
Climate zones: Cool, temperate

Leakage

Internal leakage: 0.72 %
External leakage: 0.56 %

Acoustic duct

Outdoor air: 36.1 dB(A)
Supply air: 51.6 dB(A)
Extract air: 36.0 dB(A)
Exhaust air: 51.1 dB(A)

Dimensions

Back to list