Component Database

English Deutsch polski 简体中文


Ventilation system (capacity < 600 m3/h)
Dantherm HCV460-P2

Image of 1704vs03: Dantherm HCV460-P2
Component id: 1704vs03
Manufacturer: Dantherm A/S
Air flow range from: 106 m3/h
To: 270 m3/h
Heat recovery rate: 87 %
Specific electric power: 0,34 Wh/m3
Efficiency ratio: 0,72
Humidity recovery: 0 %
Sound level of unit: 55,0 dB(A)
Climate zones: Ψυχρή, εύκρατη
Certified since: 03/11/2021

Leakage

Internal leakage: 0,89 %
External leakage: 0,16 %

Acoustic duct

Outdoor air: 68,0 dB(A)
Supply air: 58,0 dB(A)
Extract air: 66,0 dB(A)
Exhaust air: 58,0 dB(A)

Back to list

Ανακοίνωση νομικού περιεχομένου | Αποποίηση ευθυνών | Πολιτική απορρήτου