Component Database


Ventilation system (capacity < 600 m3/h)
novus 300

Component id: 0302vs03
Manufacturer: PAUL Wärmerückgewinnung GmbH
Air flow range from: 121 m3/h
To: 231 m3/h
Heat recovery rate: 93 %
Specific electric power: 0.24 Wh/m3
Efficiency ratio: 0.75
Humidity recovery: 0 %
Sound level of unit: 43.0 dB(A)
Climate zones: Cool, temperate

Leakage

Internal leakage: 0.54 %
External leakage: 1.43 %

Acoustic duct

Outdoor air: 47.2 dB(A)
Supply air: 64.9 dB(A)
Extract air: 46.0 dB(A)
Exhaust air: 64.8 dB(A)

Back to list