COM4plus CL10
Certified since | Nov. 18, 2016 |
Climate zone | Cool, temperate |
Performance Number | - |
at external pressure | 274 Pa |
available external pressure (with installed filters) | 224 Pa |
air flow range from… | 1700 m3/h |
to… | 2300 m3/h |
Heat Recovery Rate | 79% |
Specific Electric Power | 0.44 Wh/m3 |
Humidity Recovery (Winter) | 0% |
Humidity Recovery (Summer) | -% |
Width | 1760.0 mm |
Height | 1080.0 mm |
Depth | 1265.0 mm |