| Component id: | 0319vs03 |
|---|---|
| Manufacturer: | WERNIG KG |
| Air flow range from: | 60 m3/h |
| To: | 150 m3/h |
| Heat recovery rate: | 92 % |
| Specific electric power: | 0.42 Wh/m3 |
| Efficiency ratio: | 0.67 |
| Humidity recovery: | 0 % |
| Sound level of unit: | 49.0 dB(A) |
| Climate zones: | Cool, temperate |
| Internal leakage: | 2.84 % |
|---|---|
| External leakage: | 0.8 % |
| Outdoor air: | 64.7 dB(A) |
|---|---|
| Supply air: | 57.2 dB(A) |
| Extract air: | 54.1 dB(A) |
| Exhaust air: | 67.1 dB(A) |