Component id: | 1362vs03 |
---|---|
Manufacturer: | Brink Climate Systems B.V. |
Air flow range from: | 70 m3/h |
To: | 313 m3/h |
Heat recovery rate: | 89 % |
Specific electric power: | 0.2 Wh/m3 |
Efficiency ratio: | 0.74 |
Humidity recovery: | 0 % |
Sound level of unit: | 51.0 dB(A) |
Climate zones: | Cool, temperate |
Certified since: | March 5, 2019 |
Internal leakage: | 1.3 % |
---|---|
External leakage: | 1.1 % |
Outdoor air: | 56.5 dB(A) |
---|---|
Supply air: | 65.5 dB(A) |
Extract air: | 59.5 dB(A) |
Exhaust air: | 63.0 dB(A) |