Component id: | 0321vs03 |
---|---|
Manufacturer: | WERNIG KG |
Air flow range from: | 73 m3/h |
To: | 109 m3/h |
Heat recovery rate: | 89 % |
Specific electric power: | 0.36 Wh/m3 |
Efficiency ratio: | 0.67 |
Humidity recovery: | 0 % |
Sound level of unit: | 52.9 dB(A) |
Climate zones: | Cool, temperate |
Certified since: | Sept. 24, 2012 |
Internal leakage: | 2.37 % |
---|---|
External leakage: | 1.49 % |
Outdoor air: | 33.3 dB(A) |
---|---|
Supply air: | 61.1 dB(A) |
Extract air: | 39.1 dB(A) |
Exhaust air: | 59.7 dB(A) |